Switching does not cause early wear of circuit breakers; rather, it is more common for a circuit breaker to be used less than 100 times during its life cycle, much less than the regulatory requirements. In most cases, these failures are caused due to overheating resulting from moisture or the circuit breakers being used to protect faulty circuits from the beginning of their installation.
According to my experience, six mechanisms are involved in nearly all failures of circuit breakers as seen in service reports. Out of these six mechanisms, five can be seen before a failure occurs.
The simple response to this inquiry would involve the heat built up at a bad connection and later regular working of the device, humidity, and corrosion problems, problems with device quality, such as federal pacific Stab Lok and Zinsco systems, incorrect device usage based on load as well as voltage spike much worse than damage from other things happening inside GFCI and AFCI devices. Most of the time the device acts as the messenger, but the true cause usually involves issues with connections, location, or circuit.

Copper moves . Aluminium moves even more. A connection tightened to the recommended torque value at the time of installation may loosen after twenty years of heat cycling, and this will lead to an increase in temperature of the connection itself, which will cause further loosening and even more heating of the joint.
Failure happens gradually and is not easily noticed from a glance at the back of the panel. So what you see at the end is insulation material with discoloration along with terminal lugs and a breaker with a “softened” housing. In other words, what you can’t see up until the point when it starts arcing is the inside of the connection joint.
There are two ways to prevent the problem. First, torque to the value written on the equipment or the panel label, not “firm,” and second, re-torque whenever any servicing is performed because a twenty-year serviceable panel will have different terminations from the original ones. A thermal imaging survey identifies hot spots in a pane and it takes around one minute to conduct the survey for one panel. That is the service our technical team performs before recommending any replacement.
Aluminium conductors should be given a separate notice. It is important to have a device which is specified for aluminium conductors, as well as an antioxidant material required by the manufacturer and a torque wrench instead of a screwdriver. If a breaker rated for copper is attached to an aluminium feeder, problems are likely to arise once there is a load on the circuit.
This is why after years of nuisance tripping, a breaker may have the opposite effect of working better over time. It is also why simply “resetting it” is not the proper course of action, if a circuit trips regularly.A standard thermal-magnetic device, such as this single-pole 32 to 63 A MCB, is built for thousands of operations, but not for thousands of fault interruptions.
There is a clear connection between water and electricity, but the process of failure here is more gradual and less spectacular compared to that of other methods. Humidity condenses on cold busbars, and that condensation forms a film containing dirt and salts which has a little bit of conductivity. The first sign of failure is nuisance tripping during seasons of high humidity, while the second is the corrosion (at the point of contact) that leads to an increase of resistance and starts the heat cycle described above in this paper.
Typical cases of this type occur with panels situated in garages, outbuildings, basement and outdoors, and the solution to the problem is proper enclosure with the suitable IP rating instead of just covering the panel with plastic sheet.A watertight board rated for dusty and wet locations, such as this IP65 modular distribution board, keeps the condensation cycle on the outside where it belongs.
One particular risk: a panel that has been submerged, even if just for some time, should be replaced instead of dried. Water will get to the internal clearance of every device, and the residue left is conductive.

There are three variants of this error that are commonly made in practice.
The two panel brands of the middle of the 20th century have a known record of failure that cannot be solved by simply swapping breakers: Stab-Lok by Federal Pacific and Zinsco. Both brands have been associated with devices that have failed to trip in case of fault, which has led to an increase in litigation and regulation.
When it comes to any panel bearing either brand name, it would be best to have it checked by a licensed electrician and replaced instead of replacing just the faulty breaker. The same goes for Pushmatic panel breakers, which have been outdated altogether and which work with an unfamiliar bus design, which makes them some of the least used breaker boards by modern electricians.
Identifying a panel involves more than just identifying a breaker. The printing conventions are different enough that sometimes it becomes more convenient to attach a photo of the name of the panel.
A lightning strike or event of switching utility creates pulses of several microseconds and several kilovolts. Thermal and magnetic breakers are incapable of functioning during the microsecond pulses as they take far too short time to heat up the bimetallic strip. However, the pulse destroys insulation of the winding of the motor and control boards and even destroys the electronic components of the GFCI, AFCI, or smart breaker.
That is why sometimes a house can have functioning circuit breakers and yet have three completely ruined GFCIs after a storm.The protection that prevents it is a surge protective device at the panel, sized to the exposure: a Type 1+2 SPD with a 50 kA maximum discharge current for a service with overhead supply, a smaller Type 2 device for a buried service in a low-lightning area.

The circuit breaker is not resetting itself, is tripping while it was unloaded or is getting hot and smells burnt. While old age is a reason to examine a breaker, it is not necessarily the reason to change it.
The weakening joint leading to heat build-up in an electrical component. In general, the device has suffered failure due to being improperly tightened at the moment of installation.
Circuit breakers are not so much common as they are the kind of thing that every electrician has to carry replacements for—but they are really rare relative to their numbers in service. Most circuit breakers go on for decades without any problems.
For regular thermal-magnetic circuit breakers, it is about 25 to 30 years. GFI and AFCI devices, however, tend to fail significantly sooner because of their electronics and technology.
A circuit breaker could malfunction in different ways. It can break down due to high heat, moisture, or flawed connectors. However, only one type of breakdown can happen inside the apparatus, while the other two are happening outside it, at the panel. Therefore, replacing the breakers but not repairing the junction is a costly mistake that is often made in the industry.
If a panel keeps tripping, provide us with its nameplate, circuit information, and bus picture.